| Rectifiers |

|
Single
Branch
- Natural convection
cooling
- Charge of Lead-acid,
Ni-Cd and Sealed Type Batteries
- Optional output diode
- High efficiency
- High reliability
|
|
Electrical
specifications |
|
Input |
Voltage (Vac) |
230 1Ph
400 3Ph |
|
|
Voltage range |
-15% ÷ +15% |
|
|
Frequency |
50 or 60 Hz |
|
|
Frequency range |
-5% ÷ +5% |
|
|
Inrush current |
< 8 In |
|
|
Efficiency |
24Vdc about 85%
48Vdc about 90%
110Vdc about 93%
220Vdc about 93% |
|
|
Protection |
Over-Under-Voltage |
|
Output |
Voltage (Vdc) |
24, 48, 110, 220 |
|
|
Nominale power (KW) |
Up to 100 |
|
|
Static regulation |
< 1% |
|
|
Dynamic regulation |
< 10% |
|
|
Psophometric noise |
< 3mV |
|
|
Ripple |
< 1% RMS |
|
|
Protection |
Over-voltage, current |
|
|
Acoustic noise |
< 50dBa at 1 meter |
|
|
Temperature (working) |
-10°C ÷ +50°C |
|
|
Temperature (storage) |
-25°C ÷ +70°C |
|
|
Relative humidity |
< 95% at 40°C |
|
|
MTBF |
140,000 hr at 30°C |
|
|
Dimensions |
600÷1000x600x2000 mm (WxDxH) |
|
|
Altitude |
< 1000 m |
|
|
Construction |
Free standing floor metal cabinet |
|
|
Normal operation |
The rectifier is automatically set in
floating or boost charge according to battery condition. The load is
directly connected to the rectifier and to the battery, therefore it
must be able to stand the voltage variation due to the charging
conditions. |
| Rectifiers |
|
Emergency operation |
In case of AC voltage loss the battery
assures the load supply.
When AC supply is restored, normal operation is automatically reinstated. |
|